Home » LPG Tank » LPG tank product installation

LPG tank product installation

1) The foundation size of the equipment installation foundation should be consistent with the as-built drawings of the product, the height of the installation foundation plane from the ground shoul...
Rated 4.9/5 based on 452 customer reviews
Share:
Content

1) The foundation size of the equipment installation foundation should be consistent with the as-built drawings of the product, the height of the installation foundation plane from the ground should not be less than 1000mm, and the saddle foundation plate at the sliding end should be configured according to the requirements of Appendix C of JB/T4712.1-2007. The user shall prepare 4 pieces of anchor bolts, specification M20, material: Q235, and the length of the pre-embedded outrigger base plate is 70mm.

 

  • The installation base plane should be inclined with an inclination of 3/1000 so that the sewage outlet is at the low end.
Inquiry


    More LPG Tank