Home » LPG Tank » LPG gasification station tank safety technology operation regulations

LPG gasification station tank safety technology operation regulations

The valve on the tank should keep the switch flexible, tight and non-leakage, according to the process needs to open and close the valve, arbitrary operation is strictly prohibited.

Rated 4.5/5 based on 367 customer reviews
Share:
Content

First, the underground storage tanks for the next canning or maintenance after the next production, must be replaced, so that the oxygen content of the tank is less than 3%, before filling.
Second, the tank should strictly control the liquid level below 85%, the pressure should be less than 1.8MPA.
Third, the safety valve should be calibrated, the value of the tank design pressure, at least once a year calibration, level gauge, pressure gauge should be kept sensitive, failure and damage should be replaced immediately, the pressure gauge calibration once a year.

Inquiry


    More pressure vessel