External inspection, internal and external inspection, and complete inspection are the three categories of periodic storage tank inspections.

Rated 4.8/5 based on 291 customer reviews
Share:
Content

Inspection cycle should be determined according to the technical status of the equipment and the use of conditions as appropriate, but the external inspection at least once a year, internal and external inspection at least once every three years, comprehensive inspection at least once every six years. If the use of the tank has reached 15 years, should be every two years for an internal and external inspection; if the use of the period has reached 20 years, should be at least once a year internal and external inspection. After regular inspection of the tank, the inspection report by the inspector, indicating whether the tank can continue to use, or the need to take special monitoring and other measures. The inspection report should be stored in the technical file of the tank.