Kosa kati ya kiwango cha kioevu kilichoonyeshwa na kipimo cha shinikizo la pointer la tank ya kuhifadhi na kiwango halisi cha kioevu cha tank ya kuhifadhi ni kubwa sana. Solution: open the balance valve of the storage tank → close the gas phase and liquid phase instrument valves of the storage tank at the same time → use an explosion-proof wrench to relieve the pressure in the instrument pipe (if the liquid level gauge is normal, the pointer of the liquid level gauge should be at the 0 scale position) → if the liquid level The pointer of the level gauge is around the 0 scale but not at the position of the 0 scale. Kwa wakati huu, fungua paneli ya glasi ya kiwango cha kioevu na utumie screwdriver ndogo ya gorofa kufanya marekebisho ya sifuri ya mitambo hadi pointer itakaporudi kwa sifuri → tumia wrench ya mlipuko-ili kurejesha nafasi ya zamani ya disassembly → Fungua sehemu ya gesi na sehemu ya kioevu ya valve ya chombo cha kuhifadhi → karibu na kiwango cha kioevu cha gorofa ya glasi;